PowerFlex 700L Technical Data
Publication 20L-TD001A 31
Frame 3B Control Terminal Locations
Frame 3A/3B Control Terminal Specifications
Item Name Description
Wire Size Range
(1)
(1)
Maximum/minimum sizes that the terminals will accept - these are not recommendations.
Recommended Tightening
Torque (+
10%)
Wire Strip
Length
Wire
TerminalMaximum Minimum
➊
PowerFlex 700 Vector Control or
PowerFlex 700S Phase II Control
Cassette Terminal Blocks
See PowerFlex 700 Series B Tech Data (publication 20B-TD001) or
PowerFlex 700S Tech Data (publication 20D-TD002) respectively for details.
➋
Active Converter Cassette
Terminal Blocks — P1 & P2
Active Converter AC power and
control wiring
3.3 mm
2
(#12 AWG)
0.3 mm
2
(#22 AWG)
0.8 N•m (7 lb•in) 8 mm
(0.31 in.)
not
applicable
➌
SHLD Terminal Terminating point for control
wiring shields on Power Module
2.1 mm
2
(#14 AWG)
0.3 mm
2
(#22 AWG)
1.4 N•m (12 lb•in) 10 mm
(0.39 in.)
not
applicable
➍
Terminal Blocks — TB5 and TB6 Power Module control wiring 4.0 mm
2
(#10 AWG)
0.2 mm
2
(#24 AWG)
1.4 N•m (12 lb•in) 8 mm
(0.31 in.)
not
applicable
PORT
MOD
NET A
NET B
24 VDC
TB5
DC POSITIVE
DC NEGATIVE
1 120 VAC
2 PRECHARGE COIL
6 INDUCTOR OVERTEMP
WIRE RANGE:
24-10 AWG
(0.2-4 MM)
4 PR HARGE FEEDBACK
ATE ENABLE
STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)
POWER
STS
Coolant Outlet
Coolant Inlet
➊
➋➌
➍
(Drive shown with
doors removed)