16EN -
Setting Heating limit flow temperature
Index - String
MIN
value
MAX
value
Parameter function
30°C 70°C
The heat pumps monitor this set temperature (input or output), beyond which the com-
pressor is switched off immediately and automatically; this threshold is called FORCE-OFF.
Setting the Reset hysterisis following limit
Index - String
MIN
value
MAX
value
Parameter function
0.5°C 20°C
In heating, this is the temperature threshold below the force-off, which reactivates the
start-up of the compressor after the switching off for force-off.
Setting integral time
Index - String
MIN
value
MAX
value
Parameter function
0
secon-
ds
999
secon-
ds
The units possess an advanced logic for controlling the processed water temperature;
the logic prevents the system arriving at a point of equilibrium at a higher or lower tem-
perature compared with the one set in the work setting. Remember that an increase in
the integration time weakens the effect of the integral control.
Setting derivative time
Index - String
MIN
value
MAX
value
Parameter function
0
secon-
ds
120
secon-
ds
Time within which the input water temperature is checked to estimate the load on the
system; if the band on the setting value is exceeded within this time, the unit will be acti-
vated.
Setting the freeze protection alarm temperature
Index - String
MIN
value
MAX
value
Parameter function
-50°C 20°C
In the units it is possible to set a threshold for the freeze protection alarm; this value spe-
cifies at what temperature the freeze protection alarm is activated. Remember that, to
modify the freeze protection parameter, the corresponding dip-switch must be activated
(see the dip-switch configuration table).
Setting frost protection mode
Index - String
MIN
value
MAX
value
Parameter function
04
In the units, it is possible to set a safety control on the water output temperature; on the basis of the value assi-
gned to this parameter, the anti-freeze electric heater is managed as follows:
• value 0, freeze protection electric heater absent;
• value 1, freeze protection electric heater installed and working only with machine in heat or cool mode;
• value 2, freeze protection electric heater installed and working also in standby, but switching on the pump;
• value 3, freeze protection electric heater working in standby without the pump being activated;
• value 4, with external air temperature less than 3°C, the pump is activated for 2 minutes every 30, to moni-
tor the temperature of the water throughout the system.